Gutor PxW AC UPS System

Gutor

Gutor PxW AC UPS System
PEW 5 – 200 kVA single phase; PDW 10 – 220 kVA three phase
Higher ratings on request


Request Information
Standard configuration
• Single UPS
• UPS output voltage
º single phase: 1x230 V
º three phase: 3x400/230 V
• Rectifier input voltage: 3x400 V +10/-10%
• Bypass input voltage
single phase: 1x230 V +10/-10%
three phase: 3x400/230 V +10/-10%
• Frequency: 50 Hz +/- 6%
• Six-pulse Rectifier with isolation transformer
• Rectifier sized for output PF = 0.8
• Rectifier input switch
• Fixed charging voltage IU characteristic
• Static switch EN Bypass (line power side) with additional
backfeed protection
• LC display unit with additional alarm LEDs
• Alarm relays for battery operation and common alarm
• Bottom cable entry
• Ground terminal
• N+1 monitored two-speed fans
• Ambient temperature range from -10 to +40 °C
• Protection IP20
• Painting pebble gray, RAL 7032 structured
• Battery MCCB optional in UPS
• Manual Bypass Switch three position in UPS
Typical single-line drawing
Battery voltage and UPS ratings
Single phase drawing
Higher ratings and other voltages on request
■ single phase three phase
Options
• Parallel redundant configuration
• Other input voltages
three phase: 190 – 690 V
• Other output voltages
single phase: 110 – 288 V
three phase: 190 – 690 V
• Frequency 60 Hz +/- 6%
• 12-pulse Rectifier with isolation transformer
• Oversized rectifier
• Rectifier fuse
• Bypass input switch or MCCB
• Rectifier input MCCB
• Sensor for temperature dependent battery charging voltage, recommended for sealed batteries and wide temperature range
• Battery temperature alarm
• Diode for reverse polarity protection
• Rectifier output isolator/circuit breaker
• Battery fuse in UPS
• Battery fuse box
• Battery MCCB box
• Inverter input isolator/circuit breaker
• Oversized inverter
• Static Switch EA (Inverter side)
• Battery Monitor (programmable battery data)
• Battery asymmetry supervision
• AC and DC ground fault alarm
• RS-232/485 interface (event log download)
• RJ-45 Ethernet port for Web browser based monitoring
• RS-485 Modbus Protocol (slave)
• External time synchronization
• Top and/or bottom cable entry
• Space heaters
• Ventilation 100% redundant
• Panel lighting
• Ambient temperature maximum +55 °C
• Allowable altitude up to 4,000 m above sea level
• Protection up to IP52
• Other colors
• Bypass isolation transformer
• Bypass stabilizer with isolation transformer
• Black start facility
• Key switch on front panel
• Additional analog meters 96x96, cl. 1.5
º Set with VM DC, AM Bat and output FM, VM, and AM
º Set with Input VM and AM with select switch
º kW of output
º Power factor
• Relay board A077, 16 fail-safe NO / NC contacts:
º Rectifier line power fault – Ground fault – DC Inverter fuse blown
º DC out of tolerance – 5x options – Bypass line power fault
º Rectifier fuse blown – Fan failure – Power supply unit fault
º Battery discharged – Overtemperature
• Relay board A078, 16 fail-safe NO / NC contacts:
º EA inhibited – Battery disconnected – Inverter ON
º EN inhibited – Battery – Boost charge operation
º Manual Bypass ON – Rectifier failure – Rectifier ON
º Asynchronous – EA ON – External horn
º Inverter fault – EN ON – Overload Inverter/Bypass
Additional options are available on request

Relate Product